The MEC attenuators are controlled by IOC ioc-xrt-mecppatt-ims [running ioc/xrt/ims/R2.2.9] The host machine for this ioc is the RHEL5 Supermicro Atom ioc-xrt-mec-mot1 , (subnet cds-lfe.pcsdn) which runs four other IOCs:
...
It's pulling in information from PVs that are clearly not on the MEC subnet,.
- m3h_switch.db
record(m3h, "XRT:M3H:SWITCH")
...
- field(DESC, "XRay to Main/MEC Switch")
- field(ERBV, "HXX:HXM:MMS:01:EN:POSITIONGET" )
- field(XUTS, "CXI:R48:EVR:41:CTRL.SEVR" )
- field(XUTR, "CXI:R48:EVR:41:CTRL.DG0P" )
- field(DSOS, "HFX:DG2:STP:01:OPEN.SEVR" )
- field(DSO, "HFX:DG2:STP:01:OPEN" )
- field(DSCS, "HFX:DG2:STP:01:CLOSE.SEVR" )
- field(DSC, "HFX:DG2:STP:01:CLOSE" )
- field(BRSS, "PATT:SYS0:1:MPSBURSTCTRL.SEVR" )
- field(BRST, "PATT:SYS0:1:MPSBURSTCTRL" )
- field(MUTC, "HXX:HXM:MMS:01:UTC" )
- field(MSEV, "HXX:HXM:MMS:01.SEVR")
- field(MDMV, "HXX:HXM:MMS:01.DMOV")
- field(MRBV, "HXX:HXM:MMS:01.RBV" )
- field(MVAL, "HXX:HXM:MMS:01.VAL" ) f
- field(SCAN, "5 second") }
record(calcout, "XRT:M3H:SWITCH:SCAN") {
field(DESC, "Manage the Scan Rate")
field(INPA, "XRT:M3H:SWITCH.MOVE CPP" )
field(OUT, "XRT:M3H:SWITCH.SCAN")
field(CALC, "(A==0)?4:7")
field(OOPT, "On Change")
field(DOPT, "Use CALC" )