- Ensure the S21 LCS cooling system has sufficient capacity for the SAGAs.
- The cooling system has sufficient capacity if the current usage is at or below 29 kW 11 kW.
- Open the archiver (FACETHOME→Archive Viewer) and load (File→Open) ‘S21_LCS_SAGAs_July_2021.xml’ file to load the correct PVs for the S21 LCS chiller.
- Click the plot button on the middle right of the panel.
- The black line is the ‘chiller load’ in kW. You may have to adjust the range for chiller load using the min/max buttons above the plot. The black line should be below 11 29 kW when the SAGAs are off.
- The red line (the input water temp) should be < 77 degrees Fahrenheit. It is usually at 63F or below.
...