Can check light levels going into the xpm by looking at EPICS variables like this:
Code Block |
---|
(ps-4.1.2) tmo-daq:scripts> pvget DAQ:NEH:XPM:0:SFPSTATUS DAQ:NEH:XPM:0:SFPSTATUS 2021-01-13 14:36:15.450 LossOfSignal ModuleAbsent TxPower RxPower 0 0 6.5535 6.5535 1 0 0.5701 0.0001 0 0 0.5883 0.7572 0 0 0.5746 0.5679 0 0 0.8134 0.738 0 0 0.6844 0.88 0 0 0.5942 0.4925 0 0 0.5218 0.7779 1 0 0.608 0.0001 0 0 0.5419 0.3033 1 0 0.6652 0.0001 0 0 0.5177 0.8751 1 1 0 0 0 0 0.7723 0.201 |
XPM Timing Links Not Locking
If XPM links don't lock, here are some past causes:
- check that transceivers (especially QSFP, which can be difficult) are fully plugged in.
- for opal detectors:
- use devGui to toggle between LCLS1/LCLS2 timing (we should put this in the opal drp exe)
- hit TxPhyReset in the devGui (this should now be done in the opal drp executable)
- for timing system detectors: run "kcuSim -s -d /dev/datadev_01", this should also be done when one runs a drp process on the drp node (to initialize the timing registers). the drp executable in this case doesn't need any transitions.
- hit Tx/Rx reset on xpmpva gui (AMC tabs).
...