Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

  • Place database QR sticker on HSIO board and follow instructions on Documentation page.
  • Place database sticker on TTC board and follow same instructions.
  • DTM already has database page.
  • If there is an RTM that goes with this HSIO, create database page for it too.

Electrical tests:

  • Download HSIO_C03-xx Power Up.xlsx
  • Save (replace xx with board number).
  • Download Map for probe locations.
  • Run resistance check entering values in excel file.
  • If values are okay proceed to voltage check, else put aside for re-work.
  • Load FPGA with this HsioPowerOn_00000001.bit file.
  • Power board with 12V and 0.5 Amp current limit, check that current limit not reached - should be between 0.2 and 0.3 amps.
  • Check voltages and record in the excel file.
  • Upload excel file to database page created above (scan QR code to find page).
  • If okay proceed to functional test, else put aside for re-work.

...