Check dry air is flowing, and all interlock inputs are plugged in. Both chillers and MPOD should be powered but not running. Interlock board should be off.

Start Test MPOD interlock: With the interlock board still off, start EPICS controls . Verify and verify that MPOD channels cannot be turned on with the interlock board off.

Setup SVT chiller: Set SVT chiller setpoint using its touchscreen. When done, switch to remote RS-232 control (Menu->Connect Unit->Remote control). Verify watchdog is enabled (Menu->Connect Unit->Digital Interfaces).

Setup FEB chiller: Start FEB chiller and adjust setpoint, then stop the chiller.

Turn on the interlock board. : Green LED should turn on immediately; MPOD trip LED (third from top) should clear as chillers start. The other LEDs should stay off.

...

Stop the Arduino monitor script on hpstracker (this is not necessary if you don't mind it sending alarm tweets).

Take the SVT chiller off of remote control (Menu->Connect unit->Remote control). Check the setpoint and make sure it's what you want.

...