Interlock board
Inputs:
- HTM2500LF temperature+humidity sensor inside Lexan box
- Flow switch in cooling system return line
- RS-232 connection to chiller - status, set T, measured pressure/flow/T
Thresholds:
- Ambient T inside SVT Lexan box < 25 C (set in Arduino script)
- Ambient RH inside SVT Lexan box < 5 % (set in Arduino script)
- Cooling system flow > 20 GPH (adjustment screw on flow switch)
Logic:
- Check inputs every 1 s; if any input is abnormal, trip and stay tripped (must reset Arduino board to clear)
Outputs:
- RS-232 to chiller: if tripped, send "stop" command every 1 s
- Interlock to CAEN crate (5V normal, 0V tripped) - trip turns off all outputs immediately