QUICK HELP

To completely restart this feedback when all is lost...

1) STOP the feedback, 

2) verify the State Setpoints are set to values you want - you can type them in under the Setpoints column.

---The L2 Chirp setpoint (in grey) should be equal to the L2 Chirp readback at the lower right.

3) verify the Actuator Setpoints are set to values you want - you can type them in under the Setpoints column whenever the FCOM column indicates it is OFF

4) ZERO ACTUATOR OFFSETS - button in top section; this sets all the LLRF offsets to zero for feedback stations L0B, L1S, L2 and L3

5) disable all individual states DL2 Energy, BC2 Energy and Chirp, BC1 Energy and Chirp, DL1 Energy

6) START the feedback - it will display messages as it connects to actuators,

7) enable each state one at a time starting with DL1 Energy - you can watch them start up on the Plots...

Help for Longitudinal Feedback

...