Table 1.8

Value

Device Type

Controllable

ACSW

AC Switch

Y

CSWH

aTCA Carrier Switch

Y

GPIB

GPIB/LAN Gateway

Y

RTR

Router

N

SWH

Ethernet Switch

N

SCOP

Scope

N

TS

Terminal Server

Y

UPS

Uninterruptible Power Supply

N

WKUP

Walk-up ethernet connection

N

IOC

EPICS IOC

Y

PLC

Programmable Logic Controller

Y

PSC

Power Supply Controller

Y

CAMR

Camera for Beam Line Optics

Y

CRAT

Intelligent VME Crates

Y

PC

Computer that is not an IOC

Y

...

Table 1.12

Database Name Subsystem Prefix

Display and Database File Name Subsystem Prefix

Subsystem

CD

generic 

Controls Department, for development only!!

LS

lasr

Laser Steering

PM

prof

Profile Monitor

IM

curr

Current Monitor

BL

blen

Bunch Length Monitor

BP

bpm

Beam Position Monitor

MC

mc

Motion Control

CL

coll

Collimator

CV

CAMAC-to-VME

AM

am

Alignment Mirror

MG

mgnt

Magnet

EV

evg or evr

Event (Timing) System

FC

rf/energy

Frequency Counter/Flip Coil

RF

rf

Low-Level RF Master

RP

rf

Low-Level RF PLL

RC

rf

Low-Level RF PAC

RD

rf

Low-Level RF PAD

MP

mps

Machine Protection System

NW

ntwk

Network Device, terminal servers, switches routers, scopes, function generators, ...

PP

pps

Personnel Protection System

BC

bcs

Beam Containment System

EQSP

eq

 

Shared platformEquipment: roaming oscilloscopes, function generators, etc. If equipment is to be used for a specific subsystem, then use the subsystem prefix. 

TM

temp

Temperature Monitor

TR

toro

Toroid

TZ

thz

TeraHertz System

VA

vac

Vacuum

WA

wat

Water and HVAC

WS

ws

Wire Scanner

FB

fbck

Feedback

AD

ads

Alignment Diagnostic System (Wire Position Monitors + Hydrostatic Leveling Sensors)

KY

klys

Klystron (Solenoid PS, Modulator PS, PIOP )

EX

ex

Experimental Support.

Table 1.12.1

ioc IOC type

ioc

VME IOCs

 

 

 

 

Description

eioc

Embedded IOCs

 ioc

 

 

 

 

Hard IOCs

sioc

Soft IOCs running on linux

 

 

 

 

 

vioc

Soft IOCs running on linuxRT (later eliminate and make an sioc)

Area

IN20LI21,LI20-LI30,BSY0,LTU0,LTU1,UND1,DMP1

System

Two character abbreviation for subsystem previx, see Table 1.12

 

 

 

 

 

##

Two digits, Soft ioc-s start at 00-99. All embedded adn VME IOC's start at 01-99.

 

 

 

 

 

The Attribute Field

The Attribute field consists of 12 or less alphanumeric symbols, which identify a function or parameter associated with a device.

...